Main Article Content

Abstract

ABSTRACT

 

Greenhouse cooling with fogging system is important to be studied in improving design of greenhouses. The process is not about cooling the air only but also humidifying. This study aims at evaluating the variables that contribute on error in air flow rate calculation. Furthermore, effects of enthalpy reading from the psychrometric chart on air flow rate calculation has been studied also. Herewith, parameters optimization and error analysis of the air flow rate equation were carried out. Data was taken from a multispan greenhouse which had cover material of PE 150 µm, 105.6 m wide and 205 m length, and three channels consists of 82 nozzles. The result indicates that the enthalpy has more prounounce contribution to determine the air flow rate and it follows successively by temperature and sun radiation. Thus, precise reading of the enthalpy is highly necessary to minimize error of the calculation of the air flow rate. This method of analysis is applicable to find appropriate values of enthalpy and other variables to produce optimum air flow rate in greenhouses.

 

Diterima: 1 Juni 2006; Disetujui: 21 Maret 2007

Keywords

Greenhouse Evaporative Cooling Air Flow Rate Error Minimization.